2012-02-29 09:55:2012020390
 124 COSTELLO ROAD
 NEW SFD
  
 MINIMUM 1/0 FEEDERS REQUIRED FOR 150 AMPERE SUB PANEL.
 NEC T. 310.16
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED
 WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE I.E. FOYER, GUEST
 SUITE, BEDROOM 3. NEC 210.52
 A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE BALCONY.
 NEC 210.52
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC
 406.11
  