| Plan Review Notes For Permit 12020390 |
| Permit Number |
12020390 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-29 09:55:20 | 12020390 | | | 124 COSTELLO ROAD | | | NEW SFD | | | | | | MINIMUM 1/0 FEEDERS REQUIRED FOR 150 AMPERE SUB PANEL. | | | NEC T. 310.16 | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. 2008 NEC 250.94 | | | ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED | | | WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12 | | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | | FEET IN WIDTH HAVE A RECEPTACLE I.E. FOYER, GUEST | | | SUITE, BEDROOM 3. NEC 210.52 | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE BALCONY. | | | NEC 210.52 | | | ALL RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC | | | 406.11 | | | | | | ROBERT LECKY | | | ELECTRIC PLAN REVIEWER | | | [email protected] | | | 561-805-6718 | | | |
|