2012-02-24 14:42:392821 PINEWOOD AVENUE
 PERMIT #12020388
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ANY MODIFICATIONS TO THE BUILDING SHALL COMPLY WITH
 CHAPTER 17 (EXISTING DAY-CARE OCCUPANCIES) OF THE
 FLORIDA EDITION OF NFPA 101.
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 THE SCOPE OF WORK ON THE PERMIT APPLICATION DOES NOT
 MATCH THE LARGER SCOPE OF WORK SHOWN ON THE PLANS SUCH
 AS:
 1) WALLS REMOVED FROM 3 & 4 YEAR OLD'S CLASSROOMS TO
 CREATE ONE LARGE ROOM INDICATED AS "TOTS & BABYS."
 2) STORAGE ROOM CONVERTED TO NEW CLASSROOM FOR 4 & 5
 YEAR OLDS.
 3) WALLS REMOVED FROM 2 & 3 YEAR OLD'S CLASSROOM TO
 CREATE ONE LARGER ROOM FOR 3 YEAR OLDS.
 4) SMALL STORAGE ROOM CREATED BETWEEN 3 & 5 YEAR OLD
 CLASSROOMS.
  
 PROVIDE ADDITIONAL FIRE ALARM DEVICES AND SMOKE
 DETECTION DEVICES FOR ALL AREAS EFFECTED BY THE
 RENOVATION.
  
 SPECIAL EGRESS REQUIREMENTS (ESCAPE WINDOWS, EXTERIOR
 DOORS, ETC.) ARE NEEDED FOR OCCUPIED ROOMS EXCEEDING
 250 SQ.FT. THESE DETAILED REQUIREMENTS CAN BE FOUND IN
 SECTION 17.2.11.1 (CHAPTER 17 OF NFPA 101 FLORIDA
 EDITION).
  
 BATHROOM DOOR LOCK SHALL BE DESIGNED TO BE UNLOCKED
 FROM THE OUTSIDE BY STAFF.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO
 ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTIONS.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  