| 2012-02-24 14:42:39 | 2821 PINEWOOD AVENUE |
| | PERMIT #12020388 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ANY MODIFICATIONS TO THE BUILDING SHALL COMPLY WITH |
| | CHAPTER 17 (EXISTING DAY-CARE OCCUPANCIES) OF THE |
| | FLORIDA EDITION OF NFPA 101. |
| | |
| | NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. |
| | |
| | THE SCOPE OF WORK ON THE PERMIT APPLICATION DOES NOT |
| | MATCH THE LARGER SCOPE OF WORK SHOWN ON THE PLANS SUCH |
| | AS: |
| | 1) WALLS REMOVED FROM 3 & 4 YEAR OLD'S CLASSROOMS TO |
| | CREATE ONE LARGE ROOM INDICATED AS "TOTS & BABYS." |
| | 2) STORAGE ROOM CONVERTED TO NEW CLASSROOM FOR 4 & 5 |
| | YEAR OLDS. |
| | 3) WALLS REMOVED FROM 2 & 3 YEAR OLD'S CLASSROOM TO |
| | CREATE ONE LARGER ROOM FOR 3 YEAR OLDS. |
| | 4) SMALL STORAGE ROOM CREATED BETWEEN 3 & 5 YEAR OLD |
| | CLASSROOMS. |
| | |
| | PROVIDE ADDITIONAL FIRE ALARM DEVICES AND SMOKE |
| | DETECTION DEVICES FOR ALL AREAS EFFECTED BY THE |
| | RENOVATION. |
| | |
| | SPECIAL EGRESS REQUIREMENTS (ESCAPE WINDOWS, EXTERIOR |
| | DOORS, ETC.) ARE NEEDED FOR OCCUPIED ROOMS EXCEEDING |
| | 250 SQ.FT. THESE DETAILED REQUIREMENTS CAN BE FOUND IN |
| | SECTION 17.2.11.1 (CHAPTER 17 OF NFPA 101 FLORIDA |
| | EDITION). |
| | |
| | BATHROOM DOOR LOCK SHALL BE DESIGNED TO BE UNLOCKED |
| | FROM THE OUTSIDE BY STAFF. |
| | |
| | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL |
| | AREA. |
| | |
| | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | CLIENTS. |
| | |
| | AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN |
| | BUILDING PRIOR TO OCCUPANCY. |
| | |
| | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL |
| | DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. |
| | |
| | FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY |
| | BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A |
| | COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN |
| | A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL |
| | BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO |
| | ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED |
| | CLEAR OF OBSTRUCTIONS. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE ALARM SYSTEM. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |