2012-03-09 16:55:58BUILDING PLAN REVIEW
 PERMIT: 12020388
 ADD: 2821 PINEWOOD AVE
 CONT: O/B MICHAEL T BITTAN
 TEL: (561)779-8876
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 1 OF 1, :
  
 1A) THE TITLEBLOCCK IS TO PROVIDE THE LOCATION OF
 PROJECT, PROVIDE THE ADDRESS IN THE TITLE BLOCK. FBC-B
 106.1.1.
  
 1B) PLEASE PROVIDE CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 FBC-B 106.3.5).
 DESIGN PARAMETERS
 1C) EDITION OF THE FLORIDA BUILDING CODE TO WHICH THIS
 PROJECT WAS DESIGNED.
  
 1D) MINIMUM BUILDING TYPE & SQ FT
  
 1E) BUILDING FIRE SPRINKLERED OR NOT?
  
 1F) OCCUPANCY TYPE :
  
 PLEASE NOTE THE LAST PERMIT FOR THIS LOCATION WAS
 06080228. THERE ARE ADDITIONAL CHANGES TO THE PROPOSED
 PLAN THAN IS HIGHLIGHTED AS NEW WORK. PLEASE IDENTIFY
 ALL NEW WORK PROPOSED UNDER THIS PERMIT. THERE MAY BE
 WORK THAT WAS COMPLETED WITHOUT THE BENEFIT OF A PERMIT
 AND MAY HAVE ADDITIONAL CODE ISSUES. THERE ARE
 ADDITIONAL RESTROOMS ADDED, RESTROOMS RECONFIGURED,
 WALLS AND DOORS CREATING ROOMS THAT ARE NOT IDENTIFIED
 BY NAME OR NUMBER, MAKING DIFFICULT TO IDENTIFY THESE
 AREAS.
  
 THE OWNER/ DESIGNER MAY WANT TO ASK FOR RECORD RESEARCH
 REQUEST FOR PLANS UNDER THE LAST KNOWN PERMITED WORK,
 PERMIT # 06080228 TO SEE ALL OF THE AREAS THAT ARE OF
 CONCERN THAT ARE NOT HIGHLIGHTED OR INDICATED AS NEW
 WORK.
  
 1G) LIFE SAFETY SYSTEMS
 OCCUPANT LOAD AND EGRESS CAPACITIES
  
 2) EMERGENCY ESCAPE & RECUE OPENINGS
 1026.4.1 EVERY ROOM OR SPACE GREATER THAN 250 SQUARE
 FEET (23.2 M2) IN EDUCATIONAL OCCUPANCIES USED FOR
 CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR NORMALLY
 SUBJECT TO STUDENT OCCUPANCY AND EVERY ROOM OR SPACE
 NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER THAN
 BATHROOMS, IN GROUP D OCCUPANCIES SHALL HAVE NOT LESS
 THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH THE FOLLOWING:
  
 2)1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
  
 2)2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN
 44 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 3) THE ROOM WITH BI-FOLD DOORS DOES NOT SHOW THE
 INTENDED USE. 436.2 CLOSET DOORS. EVERY CLOSET DOOR
 LATCH SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM
 INSIDE THE CLOSET.
  
 4) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL
 BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM
 THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL
 BE READILY ACCESSIBLE TO THE STAFF.
  
 5) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE
 NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY
 WITH SECTION 715.3.
  
  
 6) THE ROOM WITH THE BI-FOLD DOORS DOES NOT SHOW THE
 INTENDED USE. 436.6.1 THE FOLLOWING ROOMS OR SPACES
 SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING
 BY FIRE BARRIERS HAVING A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1-HOUR OR SHALL BE PROTECTED BY AN APPROVED
 AUTOMATIC EXTINGUISHING SYSTEM.
  
 1. BOILER AND FURNACE ROOMS. EXCEPTION: ROOMS ENCLOSING
 ONLY AIR-HANDLING EQUIPMENT.
 2. ROOMS OR SPACES USED FOR THE STORAGE OF COMBUSTIBLE
 SUPPLIES IN QUANTITIES DEEMED HAZARDOUS BY THE BUILDING
 OFFICIAL.
 3. ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS
 MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS IN
 QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
 4. JANITOR CLOSETS. THE NEW UTILITY SINK IS WITHIN THE
 SAME ROOM AS THE 2 YEAR OLDS, NOT SEPERATED BY A ONE
 HOUR ENCLOSURE WITH OPENING PROTECTIVES.
  
 7) 436.7 DETECTION AND ALARM SYSTEMS. DAY CARE
 OCCUPANCIES SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM
 IN ACCORDANCE WITH SECTION 907 AND THIS SECTION.
  
 8) FBC-B TABLE 1017.1 DAYCARE OCCUPANCY WITH AN
 OCCUPANT LOAD GREATER THAN 30 REQUIRES 1 HR RATED
 CORRIDORS WHEN THERE IS NO FIRE SPRINKLERS.
 436.8 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE
 CONSTRUCTED OF WALLS HAVING NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING.
 EXCEPTIONS:
 1. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTIONS 901.6 AND 903.3.1.1 CORRIDOR WALLS SHALL
 NOT BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS
 FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 710.
 2. WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING AN
 1-HOUR FIRE-RESISTANCE RATING WHERE TESTED AS A WALL,
 THE CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE CORRIDOR CEILING.
  
 9) ROOM LABELED TOTS AND BABIES INDICATES A NEW
 EXTERIOR DOORWAY. PLEASE PROVIDE STRUCTURAL INFORMATION
 AS TO TYPE OF EXTERIOR WALL WWOOD FRAME OR BLOCK CMU?
 HOW TTHE WALL WILL BE REINFORCED WITH COLUMNS &
 RE-INFORCING, BEAMS OR LINTELS FOR MASONRY AND WOOD
 FRAME THE NUMBER OF FULL LENGTH STUDS EACH SIDE OF THE
 DOORWAY, THE NUMBER OF CRIPPLE OR JACK STUDS, SIZE OF
 HEADER AND STRAPPING, PART OF THE MAIN WIND FORCE
 RESISTING SYSTEM.FBC-B 1609.
  
 10) THE NEW EXTERIOR DOOR WILL ALSO REQUIRE THE WIND
 DESIGN CRITERIA FBC-B 1609:
 1609.6.2 WIND DESIGN PROCEDURES
 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
 5) POSITIVE & NEGATIVE PRESSURES ON THE NEW OPENING
  
 11) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 13) FBC-B 11-4.1.6(2) ALTERATIONS TO AN AREA CONTAINING
 A PRIMARY FUNCTION.
 IN ADDITION TO THE REQUIREMENTS OF SECTION 11-4.1.6(1),
 AN ALTERATION THAT AFFECTS OR COULD AFFECT THE
 USABILITY OF OR ACCESS TO AN AREA CONTAINING A PRIMARY
 FUNCTION SHALL BE MADE SO AS TO ENSURE THAT, TO THE
 MAXIMUM EXTENT FEASIBLE, THE PATH OF TRAVEL TO THE
 ALTERED AREA AND THE RESTROOMS, TELEPHONES, AND
 DRINKING FOUNTAINS SERVING THE ALTERED AREA, ARE
 READILY ACCESSIBLE TO AND USABLE BY INDIVIDUALS WITH
 DISABILITIES, UNLESS SUCH ALTERATIONS ARE
 DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN TERMS
 OF COST AND SCOPE.
  
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
 (I) AN ACCESSIBLE ENTRANCE;
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
 (IV) ACCESSIBLE TELEPHONES;
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved