| 2012-03-09 14:54:23 | BUILDING PROVISO: |
| | |
| | 1) SHEET A1.1 INDICATES THAT THE HIGH DENSITY MOBILE |
| | FILE STORAGE SYSTEM BY OTHERS, |
| | FBC-B TABLE 1607.1 OFFICE BUILDINGS FILE STORAGE SHALL |
| | BE DESIGNED FOR HEAVIER LOADS |
| | BASED ON THE ANTICIPATED OCCUPANCY. |
| | |
| | 2) SHEET A1.3 DETAIL # 11 INDICATES A LOUNGE OR BREAK |
| | ROOM SINK, PLEASE REVIEW 2007/09 |
| | FBC-B 11-4 1-7. NOTE THAT THE HEIGHT REQUIREMENT OF 34" |
| | TOP OF COUNTER TOP. |
| | |
| | 3) PLEASE SEE NOTIFICATION: FBC-B 707.14.1 ELEVATOR |
| | LOBBIES. MEMORANDUM FROM THE |
| | BUILDING OFFICIAL & BATTALION FIRE CHIEF. |
| | |
| | (3). IF A TENANT IMPROVEMENT IS SUBMITTED WHICH |
| | PROPOSES TO RECONFIGURE A PORTION OF THE |
| | EXISTING BUILDING FLOOR AREA, WITH NO WORK BEING |
| | PROPOSED IN THE AREA OF THE ELEVATOR LOBBY, |
| | AND NO ELEVATOR LOBBY IS FOUND TO EXIST ON THE FLOOR, |
| | AND NO VALID PERMIT CAN BE EVIDENCED |
| | WHICH WAS ISSUED BETWEEN OCTOBER 1, 2005 AND DECEMBER |
| | 8, 2006, THE TENANT IMPROVEMENT |
| | PERMIT MAY BE APPROVED. THE BUILDING OWNER WILL BE |
| | NOTIFIED OF AN UNSAFE CONDITION ON THE |
| | EXISTING STRUCTURE BY THE CITY FIRE MARSHAL?S OFFICE |
| | AND ASKED TO UNDERTAKE APPROPRIATE ACTIONS |
| | TO CORRECT THE SITUATION. |
| | |