| Plan Review Notes For Permit 12020313 |
| Permit Number |
12020313 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-14 13:41:22 | PLANS DENIED | | | 1) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER | | | CONTROLS. | | | FOR FRESH AIR. 2007 FBC (M) | | | 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER | | | TABLE 403.3 | | | 2007 FBC (M) | | | 3) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS PER SECTION | | | 301.5 LABELING. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|