Text |
| 2012-02-23 10:43:54 | 303 BANYAN STREET - 3RD FLOOR | | | PERMIT #12020313 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET A4.1: VERIFY SIDELIGHT WILL HAVE A 1-HOUR FIRE | | | RATING FOR ROOM #109. | | | | | | SHEET A4.1: PROVIDE BI-DIRECTIONAL CHEVRON ON EXIT SIGN | | | IN CORRIDOR #002. | | | | | | SHEET A4.1/SHEET E1.1: LIGHTING PLAN WILL NEED TO BE | | | REVISED TO MATCH THE EXIT SIGN LOCATIONS AND CHEVRONS | | | SHOWN ON THE LIFE SAFETY PLAN. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE | | | ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|