2012-02-23 10:43:54303 BANYAN STREET - 3RD FLOOR
 PERMIT #12020313
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A4.1: VERIFY SIDELIGHT WILL HAVE A 1-HOUR FIRE
 RATING FOR ROOM #109.
  
 SHEET A4.1: PROVIDE BI-DIRECTIONAL CHEVRON ON EXIT SIGN
 IN CORRIDOR #002.
  
 SHEET A4.1/SHEET E1.1: LIGHTING PLAN WILL NEED TO BE
 REVISED TO MATCH THE EXIT SIGN LOCATIONS AND CHEVRONS
 SHOWN ON THE LIFE SAFETY PLAN.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  