| Plan Review Notes For Permit 12020282 |
| Permit Number |
12020282 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-16 11:33:30 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1. THE FOUR RESTROOMS SHOWN WILL BE REQUIRED TO BE | | | ACCESSABLE PER FBC 11-4.1.3 (11) TOILET FACILITIES: | | | IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC AND | | | COMMON USE TOILET ROOM SHALL COMPLY WITH SECTION | | | 11-4.22.... | | | | | | 2. SHEET A-5.0 - THE REAR GRAB BAR AC6 IS REQUIRED TO | | | BE 36" LENGTH. 11-4.17.6 SEE FIGURE 30 (A) | | | | | | 3. SHEET P-1.0 SHOWS 3" PIPE 1/10" PER FOOT. 1/8" PER | | | FOOT IS REQUIRED - PLUMBING 704.1 | | | | | | 4. PLEASE INCLUDE RISER DIAGRAMS FOR HOT AND COLD WATER | | | AND SANITARY 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR | | | BUILDINGS. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|