2012-02-16 11:33:30FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. THE FOUR RESTROOMS SHOWN WILL BE REQUIRED TO BE
 ACCESSABLE PER FBC 11-4.1.3 (11) TOILET FACILITIES:
 IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH SECTION
 11-4.22....
  
 2. SHEET A-5.0 - THE REAR GRAB BAR AC6 IS REQUIRED TO
 BE 36" LENGTH. 11-4.17.6 SEE FIGURE 30 (A)
  
 3. SHEET P-1.0 SHOWS 3" PIPE 1/10" PER FOOT. 1/8" PER
 FOOT IS REQUIRED - PLUMBING 704.1
  
 4. PLEASE INCLUDE RISER DIAGRAMS FOR HOT AND COLD WATER
 AND SANITARY 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
  