| Plan Review Notes For Permit 12020230 |
| Permit Number |
12020230 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-24 13:11:20 | *** PROVISO *** | | | | | | 1. PAGE M102: RTU 2 APPEARS TO BE WITHIN 10' OF AN | | | ELEVATION CHANGE EXCEEDING 30". GUARDS ARE REQUIRED AT | | | THIS OCATION PER FBC-M 304.10 | | | | | | 2. PAGE M102: ACCESS TO RTU 2 WOULD REQUIRE CLIMBING | | | OVER A ROOF ELEVATION CHANGE EXCEEDING 30". A PERMANENT | | | MEANS OF ACCESS IS REQUIRED AT THIS LOCATION PER FBC-M | | | 306.5. | | | | | | 3. PAGE M501: FLEXIBLE DUCT DETAIL CALLS FOR 1" WIDE | | | STRAP FOR SUPPORT. SUPPORTS SHALL BE MIN. 1.5" WIDE. | | | ALSO, DETAIL CALL FOR MAX. 6' SPACING BETWEEN SUPPORTS. | | | THE MAX. SPACING ALLOWED IS 5'. SEE FBC-M 603.5.6.6 FOR | | | THESE AND ADDITIONAL REQUIREMENTS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|