Plan Review Notes
Plan Review Notes For Permit 12020230
Permit Number 12020230
Review Stop E
Sequence Number 1
Notes
Date Text
2012-02-28 15:03:4712020230
 420 OKEECHOBEE BLVD.
 FISKER CAR DEALER RENOVATION
  
 PROVISO:
 PROVIDE AN ENGINEERED DETAIL FOR THE COMPLETE LIGHT
 POLE MOUNTED ASSEMBLY WHICH PROVIDES A MINIMUM WIND
 LOAD CAPABILITY OF 140 MPH.
 PROVIDE THE SPECIFICATION AND LISTING FOR THE FISKER
 BATTERY CHARGING STATION. PROVIDE AN ELECTRIC
 DISCONNECT FOR CHARGERS IF RATED AT MORE THAT 60
 AMPERES. NEC 625.22
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]