| 2012-02-22 13:26:38 | BUILDING PLAN REVIEW |
| | PERMIT: 12020230 |
| | ADD: 420 OKEECHOBEE BLVD |
| | CONT: DEALERSHIP SOLUTIONS |
| | TEL: (727)894-2182 |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A000 PRODUCT APPROVAL INFORMATION |
| | |
| | THE SUMMARY OF THE PRODUCT APPROVALS DOES NOT HELP IN |
| | CODE COMPLIANCE REVIEW OR IN THE FIELD FOR INSTALLATION |
| | WHEN THE FULL PRODUCT APPROVALS ARE NOT SUBMITTED. WITH |
| | THE FULL PRODUCT REPORT PLEASE CIRCLE WHICH SUB-SYSTEMS |
| | ARE TO BE INSTALLED. MANY REPORTS PROVIDE OPTIONS FOR |
| | TYPE OF GLAZING, EACH HAVING THEIR OWN TEST PRESSURES. |
| | PLEASE NOTE THE ROOFING REPORT FL 3915 COULD NOT BE |
| | LOCATED ON LINE. DEPENDING ON THE ROOFING REPORT THERE |
| | MAY BE SUB-SYSTEMS AND VARYING PRESSURES WHICH MAY |
| | REQUIRE ENHANCED FASTENING IN ZONES 2 & 3. |
| | |
| | |
| | 2) SHEET A100, 2007/09 FBC-B 503.1.2 |
| | PLEASE PROVIDE THE DISTANCE BETWEEN THE TWO BUILDINGS, |
| | ARE THESE TO BE CONSIDERED AS ONE OR TWO BUILDINGS ON |
| | THE SAME LOT WHERE FIRE RATED WALLS AND ALLOWABLE |
| | OPENINGS ARE A CONCERN? FBC-B TABLE 602 & 704.8 . |
| | |
| | 3)SHEET A401, |
| | FBC-B 106.1.2.ADDITIONAL INFORMATION, |
| | PLEASE PROVIDE ADDITIONAL INFORMATION IN REGARDS TO |
| | WHAT APPEARS TO BE A DOOR SWING? |
| | |
| | 4) SHEET A401, |
| | A) HIDDEN DOOR PLEASE INDICATE HOW THIS DOOR WILL |
| | COMPLY WITH FBC-B 11-4.13.6. |
| | THE 18 INCHES ON THE LATCH SIDE OF THE DOOR. |
| | |
| | B) PLEASE PROVIDE HOW THE HIDDEN DOOR WILL COMPLY WITH |
| | FBC-B 13.9 DOOR HARDWARE. HANDLES, PULLS, LATCHES, |
| | LOCKS, AND OTHER OPERATING DEVICES ON ACCESSIBLE DOORS |
| | SHALL HAVE A SHAPE THAT IS EASY TO GRASP WITH ONE HAND |
| | AND DOES NOT REQUIRE TIGHT GRIPPING, TIGHT PINCHING, OR |
| | TWISTING OF THE WRIST TO OPERATE. |
| | |
| | 5) SHEET A401. PLEASE REVIEW BEVERAGE BAR AND |
| | ACCESSIBLE SINK (BAR) WITH THE CABINET ONLY BEING 21 |
| | INCHES WIDE A FRONTAL APPROACH CAN NOT BE MADE, WITH |
| | THE BAR SINK BEING AGAINST THE WALL A SIDE APPROACH CAN |
| | NOT BE ACCOMPLISHED SINCE THE CENTERLINE OF THE WHEEL |
| | CHAIR WILL BE 24 INCHES FROM THE WALL. |
| | |
| | 6) SHEET A401, WATER DISPENSER, PLEASE SEE PLUMBING |
| | COMMENT IN REGARDS TO THE REQUIRED DRINKING FOUNTAIN |
| | 2007/09 PLUMBING CODE, SINCE THE FIRST DRINKING |
| | FOUNTAIN IS A REQUIRED FIXTURE THE ACCESSIBILITY CODE |
| | REQUIREMENTS APPLY 11-4.15. SAME ISSUES AS ABOVE FOR |
| | THE FRONTAL AND SIDE APPROACH. |
| | |
| | |
| | 7) SHEET A300 COVERED DISPLAY AREA INDICATES THE USE OF |
| | A STUCCO CEILING SYSTEM BUT NO ADDITIONAL INFORMATION |
| | IS PROVIDED FOR WHAT TYPE OF MATERIALS WILL MAKE UP |
| | THIS SYSTEM? |
| | THE STRUCTURAL SHEETS INDICATES THIS BUILDING IS |
| | DESIGNED AS A TOTALLY ENCLOSED BUILDING . |
| | WILL THE PRESSURES BE GREATER UNDER THIS OPEN SPACE |
| | SIMILAR TO ROOF OVER HANGS? WILL A EFIS SYSTEM BE |
| | CONSIDERED FOR THIS APPLICATION IF SO PRODUCT APPROVALS |
| | FOR THIS SYSTEM WILL BE REQUIRED. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. RULE 9N3 (31)?. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |