| 2012-03-05 13:39:41 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. THE SCOPE ON THE PERMIT APPLICATION (WINDOW |
| | REPLACEMENT) DOES NOT MATCH THE PLANS (SUNROOM). PLEASE |
| | ADDRESS. |
| | |
| | 2ND REVIEW, IT APPEARS THAT THIS IS A ROOM ENCLOSURE. |
| | PLEASE HAVE THE ENGINEER REVISE THE PLAN TO INCLUDE |
| | BUILDING CONSTRUCTION TYPE, FBC CHAPTER 5 TO DETERMINE |
| | WHETHER A FOAM EXTERIOR WALL IS PERMITTED FOR THIS |
| | STRUCTURE. NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO |
| | DEMONSTRATE COMPLIANCE. A CODE SUMMARY (BUILDING TYPE, |
| | OCCUPANCY CLASSIFICATION, BUILDING SIZE, FIRE |
| | SPRINKLERS, ETC.) MAY BE HELPFUL. SEE ALSO FBC TABLE |
| | 601. |
| | |
| | APPLICATION DESCRIPTION DOES NOT MATCH PLAN. PLAN SHOWS |
| | ENCLOSURE OF A PORCH, APPLICATION STATES 2 WINDOWS WILL |
| | BE INSTALLED IN A ROOM. IS THIS CURRENTLY A ROOM, OR A |
| | SCREEN PORCH AS SHOWN ON PLANS? |
| | |
| | 2. ADDRESSED. |
| | |
| | 3. PROVIDE A SURVEY SHOWING LOCATION OF PROPOSED |
| | IMPROVEMENT AND DISTANCE TO PROPERTY LINE, FBC R 302. |
| | |
| | NOT ADDRESSED. PROVIDE INFORMATION REGARDING DISTANCE |
| | TO THE PROPERTY LINE OR ASSUMED PROPERTY LINE, SEE FBC |
| | TABLE 602. CONTRACTOR'S NOTE THAT A SURVEY IS NOT |
| | REQUIRED AS THERE IS NO CHANGE IN FOOTPRINT IS |
| | ACKNOWLEDGED; HOWEVER, THIS DOES NOT ADDRESS THE ISSUE |
| | OF FIRE RISK TO ADJACENT STRUCTURES AS YOU ARE |
| | PROPOSING TO CHANGE THE LOCATION OF THE EXTERIOR WALL. |
| | |
| | 4. OK. |
| | |
| | NEW COMMENTS: |
| | |
| | 5. REVISE PLAN TO SHOW 1 HOUR SEPARATION REQUIRED |
| | BETWEEN THIS UNIT AND THE UNIT ABOVE, FBC 711.3. |
| | |
| | 6. IMPACT FEE ASSESSMENT WILL BE REQUIRED, 233-5025 FOR |
| | MORE INFORMATION. |
| | |
| | 7. ALL COMMENTS TO BE ADDRESSED BY A DESIGN |
| | PROFESSIONAL LICENSED UNDER FS 471 OR 481. |
| | |
| | 8. IT IS NOT CLEAR HOW THE WINDOWS ARE TO BE INSTALLED |
| | INTO THE FOAM PANELS, THIS INSTALLATION NOT COVERED BY |
| | THE PRODUCT APPROVAL. NO STRUCTURAL INFORMATION HAS |
| | BEEN PROVIDED. PROVIDE A STRUCTURAL DETAIL FOR PROPOSED |
| | INSTALLATION. |
| | |
| | |