Plan Review Notes
Plan Review Notes For Permit 12020213
Permit Number 12020213
Review Stop E
Sequence Number 2
Notes
Date Text
2012-03-15 15:17:4012020213
 2471 OKEECHOBEE BLVD.
 COMMERCIAL TENANT IMPROVEMENT
  
 THIS REVIEW HAS BEEN UPDATED IN RESPONSE TO THE REVISED
 PLANS AND CORRESPONDENCE RECEIVED 3/12/12 FROM LOUCKS
 ENGINEERING.
  
 THE PLANS INDICATE THERE ARE TWO POINTS OF SERVICE TO
 THE BUILDING WITHOUT THE MAIN SERVICE DISCONNECTS BEING
 GROUPED IN ONE LOCATION. THE ARCHITECTURAL PLANS SHOW
 ONE BUILDING. THE ONE HOUR RATED FIRE AND SMOKE TENANT
 SEPARATION DOES NOT ESTABLISH A SEPARATE BUILDING. NEC
 230.2, 230.71
 THE SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT NEEDS TO BE A LITTLE MORE SPECIFIC AS TO THE
 WORDING, SIZE, HAZARD AND TYPE OF MATERIAL. NEC 110.22,
 110.16
 THE SPACE PROVIDED FOR THE ELECTRICAL EQUIPMENT NEEDS
 TO BE DEDICATED AND PROTECTED. NEC 110.26 (F)
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  