| Plan Review Notes For Permit 12020213 |
| Permit Number |
12020213 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-03-15 15:17:40 | 12020213 | | | 2471 OKEECHOBEE BLVD. | | | COMMERCIAL TENANT IMPROVEMENT | | | | | | THIS REVIEW HAS BEEN UPDATED IN RESPONSE TO THE REVISED | | | PLANS AND CORRESPONDENCE RECEIVED 3/12/12 FROM LOUCKS | | | ENGINEERING. | | | | | | THE PLANS INDICATE THERE ARE TWO POINTS OF SERVICE TO | | | THE BUILDING WITHOUT THE MAIN SERVICE DISCONNECTS BEING | | | GROUPED IN ONE LOCATION. THE ARCHITECTURAL PLANS SHOW | | | ONE BUILDING. THE ONE HOUR RATED FIRE AND SMOKE TENANT | | | SEPARATION DOES NOT ESTABLISH A SEPARATE BUILDING. NEC | | | 230.2, 230.71 | | | THE SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | | EQUIPMENT NEEDS TO BE A LITTLE MORE SPECIFIC AS TO THE | | | WORDING, SIZE, HAZARD AND TYPE OF MATERIAL. NEC 110.22, | | | 110.16 | | | THE SPACE PROVIDED FOR THE ELECTRICAL EQUIPMENT NEEDS | | | TO BE DEDICATED AND PROTECTED. NEC 110.26 (F) | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|