| Plan Review Notes For Permit 12020213 |
| Permit Number |
12020213 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-13 15:30:05 | 12020213 | | | 2471 OKEECHOBEE BLVD. | | | COMMERCIAL TENANT IMPROVEMENT | | | | | | VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO | | | INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING | | | RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND | | | CURRENT THAT IS AVAILABLE. NEC 110.9 | | | PROVIDE DEDICATED SPACE FOR THE SERVICE PANEL BOARDS. | | | NEC 110.26 (F) | | | PRIMARY AND SECONDARY FEEDER CONDUCTORS TO THE | | | TRANSFORMER APPEAR TO BE UNDER SIZED OR TRANSFORMER IS | | | OVERSIZED FOR THE LOAD. PLEASE CLARIFY. NEC 215.2 | | | VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND | | | GROUPED IN ONE LOCATION. THE PLANS SUGGEST THIS | | | BUILDING IS ALREADY SERVED FROM ANOTHER LOCATION. NEC | | | 230.2, 230.71 | | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | | PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE | | | REQUIRED AT THE ELECTRICAL EQUIPMENT AND ELECTRICAL | | | ROOM. NEC 110.22, 110.16 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|