 2471 OKEECHOBEE BLVD.
 COMMERCIAL TENANT IMPROVEMENT
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE. NEC 110.9
 PROVIDE DEDICATED SPACE FOR THE SERVICE PANEL BOARDS.
 NEC 110.26 (F)
 PRIMARY AND SECONDARY FEEDER CONDUCTORS TO THE
 TRANSFORMER APPEAR TO BE UNDER SIZED OR TRANSFORMER IS
 OVERSIZED FOR THE LOAD. PLEASE CLARIFY. NEC 215.2
 VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND
 GROUPED IN ONE LOCATION. THE PLANS SUGGEST THIS
 BUILDING IS ALREADY SERVED FROM ANOTHER LOCATION. NEC
 230.2, 230.71
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED AT THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOM. NEC 110.22, 110.16
  