2012-02-15 12:51:261700 PALM BEACH LAKES BOULEVARD - SUITE #950
 PERMIT #12020211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE-RATED WALL/PARTITION SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE
 DETAILS OF PROPER PROTECTION.
  
 PROVIDE A FURNITURE LAYOUT.
  
 TENANT SEPARATION WALL AT COLUMN LINE 3 DOES NOT
 INDICATE IF THIS WALL HAS A FIRE RESISTANCE RATING.
  
 THE EAST WALL OF OFFICE #111 DOES NOT INDICATE A FIRE
 RESISTANCE RATING.
  
 CORRIDOR #103/#107 CREATES A DEAD-END IN EXCESS OF 50
 FEET.
  
 THE COMMON PATH OF TRAVEL NEEDS TO BE MEASURED TO THE
 STAIRWELL DOOR AS THIS IS THE LOCATION WHERE AN
 OCCUPANT HAS A CHOICE BETWEEN EXISTING STAIR #1 OR
 EXISTING STAIR #2. THIS COMMON PATH OF TRAVEL DISTANCE
 APPEARS TO EXCEED THE 100 FEET OF TRAVEL PERMITTED BY
 THE LIFE SAFETY CODE.
  
 THE NEW TENANT SEPARATION WALL AT CORRIDOR #110 MAY
 EFFECT THE MAXIMUM COMMON PATH OF TRAVEL DISTANCE AND
 DEAD-END CORRIDOR DISTANCE OF THE EAST SUITE NOTED AS
 VACANT.
  
 INDICATE THE LOCATIONS OF THE FIRE ALARM NOTIFICATION
 APPLIANCES.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  