Notes
Date Text
2012-02-28 12:18:42PROVISO:
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND 2008 NEC 250.94,
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING IN HOMES WITH GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE. 2007
 FBC R313
 ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED
 WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 ALL NEW RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC
 406.11
  