| Plan Review Notes For Permit 12020175 |
| Permit Number |
12020175 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-28 12:18:42 | PROVISO: | | | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND 2008 NEC 250.94, | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING IN HOMES WITH GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE. 2007 | | | FBC R313 | | | ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED | | | WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12 | | | ALL NEW RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC | | | 406.11 | | | | | | ROBERT LECKY | | | ELECTRIC PLAN REVIEWER | | | [email protected] | | | 561-805-6718 | | | |
|