Plan Review Notes
Plan Review Notes For Permit 12020156
Permit Number 12020156
Review Stop E
Sequence Number 1
Notes
Date Text
2012-02-10 10:00:5412020156
 2235 OKEECHOBEE BLVD.
 COMMERCIAL REMODEL
  
 PLEASE ADDRESS THE FOLLOWING ITEMS.
  
 SHEET E-3:
  
 ELECTRICAL RISER AS ILLUSTRATED FROM MAIN #1 THROUGH
 THE TRANSFER SWITCH APPEARS TO INTERCHANGE THE FEEDERS
 FOR PANEL ?DB" AND THE EMERGENCY PANEL ?EDP? AND
 ISOLATE PANEL ?DB? WHEN THE FACILITY IS UNDER NORMAL
 POWER. NEC 215.5
 VERIFY EXISTING PANELS ?DA? AND ?DB? ARE RATED FOR 800
 AMPERES. NEC 215.5
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 PROVIDE A GFCI PROTECTED RECEPTACLE FOR THE NEW WATER
 COOLER. NEC 422-52
 VERIFY THE ELECTRICAL SERVICE, WHICH APPEARS TO BE
 LOCATED IN A REMOTE STRUCTURE, MEETS THE REQUIREMENT
 FOR BONDING OF THE GROUNDED CONDUCTOR AT THE MAIN
 SERVICE DISCONNECTS AND THE REQUIREMENTS FOR GROUNDING
 OF THE SYSTEM AT THE MAIN STRUCTURE. NEC 250.24, 250.32
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED AT THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOM. NEC 110.22, 110.16
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  