| 2012-02-10 10:00:54 | 12020156 | | | 2235 OKEECHOBEE BLVD. | | | COMMERCIAL REMODEL | | | | | | PLEASE ADDRESS THE FOLLOWING ITEMS. | | | | | | SHEET E-3: | | | | | | ELECTRICAL RISER AS ILLUSTRATED FROM MAIN #1 THROUGH | | | THE TRANSFER SWITCH APPEARS TO INTERCHANGE THE FEEDERS | | | FOR PANEL ?DB" AND THE EMERGENCY PANEL ?EDP? AND | | | ISOLATE PANEL ?DB? WHEN THE FACILITY IS UNDER NORMAL | | | POWER. NEC 215.5 | | | VERIFY EXISTING PANELS ?DA? AND ?DB? ARE RATED FOR 800 | | | AMPERES. NEC 215.5 | | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | | PROVIDE A GFCI PROTECTED RECEPTACLE FOR THE NEW WATER | | | COOLER. NEC 422-52 | | | VERIFY THE ELECTRICAL SERVICE, WHICH APPEARS TO BE | | | LOCATED IN A REMOTE STRUCTURE, MEETS THE REQUIREMENT | | | FOR BONDING OF THE GROUNDED CONDUCTOR AT THE MAIN | | | SERVICE DISCONNECTS AND THE REQUIREMENTS FOR GROUNDING | | | OF THE SYSTEM AT THE MAIN STRUCTURE. NEC 250.24, 250.32 | | | PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE | | | REQUIRED AT THE ELECTRICAL EQUIPMENT AND ELECTRICAL | | | ROOM. NEC 110.22, 110.16 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|