| Plan Review Notes For Permit 12020114 |
| Permit Number |
12020114 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-03-09 09:53:18 | FBC FUEL GAS REVIEW #2 | | | DENIED: | | | | | | REVISION SUBMITTED FOR NON-ISSUED GAS PERMIT. | | | ORIGINAL GAS REVIEW WAS DENIED. DENIED COMMENTS FRON | | | REVIEW #1 BELOW: | | | | | | FBC FUEL GAS 2007 REVIEW #1 | | | | | | 1. SUBMITTED PLANS ARE COPIES OF ENGINEER SEALED PLANS. | | | PLEASE SUBMIT ISOMETRIC DRAWINGS THAT HAVE THE JOB | | | ADDRESS, THE COMPANY NAME AND SIGNATURE. | | | | | | 2. THE FOLLOWING INFORMATION WILL BE REQUIRED: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2007 FUEL GAS. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2007 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|