2012-03-29 11:49:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. OUR RECORDS SHOW THAT THE WALL HAS NOT OBTAINED THE
 LEGALLY REQUIRED INSPECTIONS. THIS MUST BE ADDRESSED
 PRIOR TO ISSUANCE OF A PERMIT TO ALTER THE WALL. PLEASE
 APPLY FOR A REISSUE PERMIT TO OBTAIN THE REQUIRED FINAL
 INSPECTION.
  
 2. OUR RECORDS SHOW A 12"X16" FOOTING FOR THE EXISTING
 WALL. IT DOES NOT APPEAR THAT THIS IS ADEQUATE TO
 SUPPORT LOADS REQUIRED FOR THE PROPOSED IMPROVEMENT.
 EITHER ENGINEERING OR CALCULATIONS WILL BE REQUIRED.
  
 3. THERE IS A PARCEL HOLD PLACED ON THIS PROPERTY WHICH
 STATES THAT NEIGHBORS REPORTED THAT THERE WAS DAMAGE TO
 THE EAST AND WEST. THIS ISSUE WILL BE ADDRESSED DURING
 THE REISSUE PROCESS FOR THE WALL PREVIOUSLY
 CONSTRUCTED.
  