| 2012-02-23 17:55:47 | RESIDENTIAL (R3) ALTERATION PLUMBING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PLUMBING FIXTURES ARE NOT PROPERLY VENTED. SANITARY |
| | RISER DIAGRAM 2/E1 ON SHEET E1 SHOWS NO VENT FOR THE |
| | WATER CLOSET, TUB AND SHOWER. IN HORIZONTAL WET-VENT |
| | SYSTEMS, NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN |
| | SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE |
| | DRAIN CONNECTION. SEE SEC. P3108.2. |
| | |
| | 2- CLEARLY SPECIFY VENT SIZES AS REQUIRED BY SEC. |
| | P3108.3. |
| | |
| | 3- REVISE SANITARY RISER DIAGRAM 2/E1. EACH FIXTURE |
| | DRAIN SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL |
| | BRANCH BEING WET VENTED OR SHALL HAVE A DRY VENT. SEC. |
| | P3108.1. |
| | ALSO, INFORMATION SHOWN ON FLOOR PLAN 1/E1 DOESN'T |
| | MATCH INFORMATION SHOWN ON SANITARY RISER DIAGRAM 2/E1. |
| | |
| | ***NOTE: PLUMBING RISER DIAGRAM MAY BE DRAWN BY THE |
| | LICENSED PLUMBING CONTRACTOR DOING THE JOB. IF DOING |
| | SO, THEN PLUMBING CONTRACTOR TO WRITE NAME, LICENSE |
| | NUMBER AND SIGN THE DRAWING. |
| | |
| | 4- SHEET E1: DETAIL 4/E1: TRAP GUARD ON FLOOR DRAIN IS |
| | NOT ALLOWED. TRAPS FOR FLOOR DRAINS SHALL BE FITTED |
| | WITH A TRAP PRIMER OR SHALL BE OF THE DEEP SEAL DESIGN |
| | AS REQUIRED BY SEC. P3201.2. |
| | |
| | |