| 2012-02-24 15:16:56 | RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW |
| | COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROPERTY IS LOCATED ON FLOOD ZONE A5 WITH FLOOD BASE |
| | ELEVATION OF 7'. FINISH FLOOR ELEVATION NEEDS TO BE AT |
| | LEAST 7'-6" AS REQUIRED BY CITY ORDINANCE SEC. |
| | 94-546(B)(1). PLEASE PROVIDE DOCUMENTATION SHOWING THE |
| | FINISH FLOOR. |
| | |
| | 2- PLEASE PROVIDE PRODUCT APPROVAL (2 COPIES) AS |
| | REQUIRED BY DCA RULE 9N-3 FOR: |
| | A) SLIDING DOORS. (1) NOA 10-0120.03 SUBMITTED DOESN'T |
| | MEET THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT |
| | ON SHEET S1. |
| | (2) NOA SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. PLEASE |
| | VISIT MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. |
| | |
| | B) OUTSWING WOOD DOOR. NOA 10-1222.03 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. PLEASE PROVIDE CURRENT ONE. |
| | |
| | C) CASEMENT WINDOW. NOA 09-1027.05 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. PLEASE SUBMIT CURRENT ONE. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 4- SHEET S1: CLARIFY WIND DESIGN CRITERIA. TWO STORY |
| | COMPONENTS AND CLADDING DESIGN PRESSURES +/- 64 PSF |
| | (WORST CASE) DESIGN PRESSURES DON'T MATCH THE DESIGN |
| | PRESSURES SHOWN ON TWO STORY DIAGRAM. PLEASE REVISE AS |
| | REQUIRED TO MATCH. REVISE POSITIVE AND NEGATIVE |
| | PRESSURES TO MATCH. |
| | |