| 2012-02-09 11:56:50 | 477 SOUTH ROSEMARY AVENUE - SUITE #228 |
| | PERMIT #12020020 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: **THIS PLAN IS BEING REVIEWED AS A CHANGE OF |
| | OCCUPANCY FROM RESIDENTIAL TO BUSINESS OCCUPANCY. |
| | |
| | PROVISO - SUBMIT REVISED PLANS |
| | |
| | SHEET M1.1 - DUCTWORK IS PASSING THROUGH A FIRE-RATED |
| | WALL FROM SUITE 316 TO SUITE 318. PROVIDE FIRE DAMPERS. |
| | |
| | FIRE-RATED WALLS SHALL BE PERMANENTLY IDENTIFIED WITH |
| | SIGNS OR STENCILING READING FIRE/SMOKE BARRIER-PROTECT |
| | ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| | SPACED NOT MORE THAN 15 FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE |
| | ALARM SYSTEM. |
| | |
| | EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC |
| | AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER |
| | COMPANY. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL |
| | OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING |
| | OPERATION. THE RELEASING MECHANISM SHALL HAVE AN |
| | OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED |
| | UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE |
| | SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND |
| | SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR |
| | TWISTING OF THE WRIST TO OPERATE. |
| | |
| | THE RESIDENTIAL STYLE FIRE SPRINKLERS WILL NEED TO BE |
| | REPLACED WITH COMMERCIAL STYLE SPRINKLERS. SPRINKLERS |
| | WILL NEED TO ADDED TO ANY SMALL CLOSETS AND RESTROOMS |
| | PER NFPA 13. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |