| 2012-02-13 15:21:29 | 315 SOUTH FLAGLER DRIVE |
| | PERMIT #12010646 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | **SHEET A0.0: PLAN STATES CERTAIN STAIRS WILL BE OUT OF |
| | SERVICE AND BUILDING OCCUPANTS WILL NEED TO |
| | "RE-DIRECTED" TO IN-SERVICE STAIRS DURING DIFFERENT |
| | PHASES OF CONSTRUCTION. SUBMIT ADDITIONAL INFORMATION |
| | AS TO HOW THE EXITING PLAN WILL BE EXECUTED AND MANAGED |
| | WITH REGARDS TO BUILDING EMERGENCY PLANS, EXISTING EXIT |
| | SIGN LOCATIONS, TEMPORARY SIGNAGE, STAFF, OCCUPANTS, |
| | VISITORS ETC. |
| | |
| | SHEET A1.11: PROVIDE NON-COMBUSTIBLE 18" DEEP DRAFT |
| | STOPS AROUND FLOOR OPENING. PROVIDE CLOSELY SPACED |
| | SPRINKLERS AROUND FLOOR OPENING. |
| | |
| | SHEET FP0.1: THE CONSTRUCTION DOCUMENTS SIGNED/SEALED |
| | BY THE ENGINEER, ESTABLISH R. DAVENPORT AS THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION DESIGN; THEREFORE, |
| | THE FIRE SPRINKLER SHOP DRAWINGS SHALL NOT BE SEALED. |
| | |
| | SHEET FP1.1: PROVIDE NON-COMBUSTIBLE 18" DEEP DRAFT |
| | STOPS AROUND FLOOR OPENING. PROVIDE CLOSELY SPACED |
| | SPRINKLERS AROUND FLOOR OPENING. |
| | |
| | |
| | GENERAL |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| | TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE |
| | SURFACE. |
| | |
| | |
| | DEMOLITION/CONSTRUCTION |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| | |
| | SMOKING SHALL BE PROHIBITED THROUGHOUT THE DEMOLITION |
| | AREAS. "NO SMOKING" SIGNS SHALL BE POSTED THROUGHOUT. |
| | |
| | SMOKING SHALL BE PERMITTED ONLY IN DESIGNATED AREAS. |
| | WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR |
| | SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |