| Notes |
| Date |
Text |
| 2012-02-06 10:53:51 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. ANCHORING DETAIL IS NOT A PART OF THE SHED DCA | | | APPROVAL. IT IS ILLEGIBLE AND DOES NOT INCLUDE WIND | | | DESIGN CRITERIA. DOCUMENTS PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS FS471. | | | | | | PROVIDE LEGIBLE ANCHORING DETAIL INCLUDING THE WIND | | | DESIGN CRITERIA TO SHOW THAT THIS PROPOSED IMPROVEMENT | | | WILL RESIST WIND LOADS FBC R301. DETAIL TO BE SIGNED | | | AND SEALED, IF APPLICABLE, BY AN INDIVIDUAL LICENSED | | | UNDER FS471, 481, 489 TO DESIGN THIS SCOPE. | | | |
|