| Plan Review Notes For Permit 12010612 |
| Permit Number |
12010612 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-01 10:08:08 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. DESIGN PRESSURES ARE TOO LOW. THIS IS LOCATED IN | | | EXPOSURE C, 140 MPH. DOOR PRODUCT APPROVAL SUBMITTED | | | HAS AD DESIGN PRESSURE LIMITATION OF +35.7/-35.7. | | | PRODUCT TO BE INSTALLED IS TO HAVE A MINIMUM DESIGN | | | PRESSURE OF +39.99/-45.3 FOR A BUILDING WHICH IS 20' IN | | | HEIGHT. CONTRACTOR TO PROVIDE BUILDING HEIGHT WHEN | | | RESUBMITTING. IF BUILDING HEIGHT EXCEEDS 20', DESIGN | | | PRESSURES WILL BE HIGHER. ENGINEERING MAY BE REQUIRED. | | | FBC1609.1. | | | | | | |
|