| Plan Review Notes For Permit 12010596 |
| Permit Number |
12010596 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-16 15:42:52 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C PER | | | 2007 FBC R 301.2.1.4.3. PLEASE REVISE THE ROOF NOTES | | | AND TRUSS LOADING NOTES ON S-1 TO SPECIFY EXPOSURE C. | | | | | | 2) THE TRUSS LOADING NOTES SPECIFY A MAXIMUM TRUSS | | | SPACING OF 12" O.C. AND THE ROOF PLAN ON S-1 SPECIFIES | | | TRUSSES 24" O.C. PLEASE CLARIFY. CITY AMENDMENTS | | | 106.1.1 | | | | | | 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | | AMENDMENTS 106.3.3 | | | | | | 4) PRODUCT APPROVALS WERE SUBMITTED FOR A SINGLE HUNG | | | WINDOW, HOWEVER, THERE DOES NOT APPEAR TO BE ANY NEW SH | | | WINDOWS SHOWN ON THE PLANS. PLEASE CLARIFY. CITY | | | AMENDMENTS 106.1.1 | | | | | | 5) FROM THE PLANS THAT WERE SUBMITTED FOR THIS | | | ADDITION, IT DOES NOT APPEAR THAT ANY REQUIRED MEANS OF | | | EGRESS OR EMERGENCY AND RESCUE OPENING AS REQUIRED BY | | | FBC R310 HAS BEEN COMPROMISED. THIS IS A LIFE SAFETY | | | ISSUE AND MUST BE IN COMPLIANCE. | | | | | | 6) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM PER 2007 FBCR ENERGY GLITCH AMENDMENTS | | | SECTION N1100.2.2 | | | | | | 7) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE | | | REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | 2012-02-01 09:42:19 | R--2 |
|