Plan Review Notes
Plan Review Notes For Permit 12010565
Permit Number 12010565
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-31 09:42:28****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE MIAMIDADE NOA PROVIDED IS INCOMPLETE. THE COVER
 SHEET WAS PROVIDED WITH MANY OTHER SPEC SHEETS,
 INCLUDING ADDITIONAL SHEETS FROM THE NOA MIXED INTO THE
 34 SHEETS PROVIDED. FAC9N-3, PROVIDE A COMPLETE
 EVALUATION REPORT, PROPERLY COLLATED, WHICH SHOWS
 DESIGN PRESSURE LIMITATIONS IF APPLICABLE. REMOVE
 UNNECESSARY SHEETS. CONFRIM THAT SPEC SHEETS ARE
 CURRENT; THE SHEETS PROVIDED ARE DATED 2002; CONFIRM
 THAT THE PAGES WHICH WILL BE A PART OF THE LEGAL PERMIT
 DOCUMENT RECORD ARE CURRENT.
  
 2. SPEC SHEETS PROVIDED HAVE MANY OPTIONS; PLEASE
 CIRCLE THE OPTION PROPOSED.
  
 3. PROVIDE A PLAN SHOWING DOOR LOCATION. INCLUDE
 INFORMATION SUCH AS CORRIDOR RATING REQUIREMENTS,
 PROXIMITY TO CORNER OF THE BUILDING, OR ANY OTHER
 INFORMATION REQUIRED TO DETERMINE CODE COMPLIANCE. A
 NOA IMPLIES THAT THE DOOR IS SUBJECT TO C&C PRESSURES,
 IS THIS CORRECT? THE FIRE RATING IMPLIES THAT THIS IS
 AN INTERIOR DOOR. DUE TO INSUFFICIENT INFORMATION
 PROVIDED, A COMPLETE CHECKLIST CANNOT BE MADE AT THIS
 TIME. IF THE DOOR IS SUBJECT TO WIND PRESSURES,
 ENGINEERING REQUIRED TO DETERMINE MINIMUM DESIGN
 PRESSURE FOR THE DOOR.
  
  