| 2012-01-31 09:42:28 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. THE MIAMIDADE NOA PROVIDED IS INCOMPLETE. THE COVER |
| | SHEET WAS PROVIDED WITH MANY OTHER SPEC SHEETS, |
| | INCLUDING ADDITIONAL SHEETS FROM THE NOA MIXED INTO THE |
| | 34 SHEETS PROVIDED. FAC9N-3, PROVIDE A COMPLETE |
| | EVALUATION REPORT, PROPERLY COLLATED, WHICH SHOWS |
| | DESIGN PRESSURE LIMITATIONS IF APPLICABLE. REMOVE |
| | UNNECESSARY SHEETS. CONFRIM THAT SPEC SHEETS ARE |
| | CURRENT; THE SHEETS PROVIDED ARE DATED 2002; CONFIRM |
| | THAT THE PAGES WHICH WILL BE A PART OF THE LEGAL PERMIT |
| | DOCUMENT RECORD ARE CURRENT. |
| | |
| | 2. SPEC SHEETS PROVIDED HAVE MANY OPTIONS; PLEASE |
| | CIRCLE THE OPTION PROPOSED. |
| | |
| | 3. PROVIDE A PLAN SHOWING DOOR LOCATION. INCLUDE |
| | INFORMATION SUCH AS CORRIDOR RATING REQUIREMENTS, |
| | PROXIMITY TO CORNER OF THE BUILDING, OR ANY OTHER |
| | INFORMATION REQUIRED TO DETERMINE CODE COMPLIANCE. A |
| | NOA IMPLIES THAT THE DOOR IS SUBJECT TO C&C PRESSURES, |
| | IS THIS CORRECT? THE FIRE RATING IMPLIES THAT THIS IS |
| | AN INTERIOR DOOR. DUE TO INSUFFICIENT INFORMATION |
| | PROVIDED, A COMPLETE CHECKLIST CANNOT BE MADE AT THIS |
| | TIME. IF THE DOOR IS SUBJECT TO WIND PRESSURES, |
| | ENGINEERING REQUIRED TO DETERMINE MINIMUM DESIGN |
| | PRESSURE FOR THE DOOR. |
| | |
| | |