| Plan Review Notes For Permit 12010550 |
| Permit Number |
12010550 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-15 13:41:59 | 2007 FBC W/2009 REVISIONS | | | | | | MECHANICAL REVIEW DENIED | | | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS FOR THE PROJECT. | | | SHOW DUCT LAYOUT AND DROP LOCATIONS, SPECIFY DUCT | | | SIZES, SPECIFY GRILL SIZES AND CFMS. SHOW RETURN | | | LOCATIONS AND SIZES. CITY AMENDMENTS 106.3.5.4 | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE WITH THE MODEL NUMBERS | | | ON THE PLANS. AMENDMENTS 106.3.5.4 | | | | | | 3) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | | RETURN AIR. | | | | | | 4) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED | | | BY 2007 FBC ENERGY GLITCH AMENDMENTS SECTION N1100. | | | | | | 5) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|