Plan Review Notes
Plan Review Notes For Permit 12010550
Permit Number 12010550
Review Stop G
Sequence Number 1
Notes
Date Text
2012-02-15 12:02:472007 FBC W/2009 REVISIONS
  
 GAS REVIEW DENIED
  
 1) THE PLANS APPEAR TO SHOW A LARGER GAS STOVE AND
 RELOCATED DRYER THAT COULD BE GAS. IN ORDER TO
 DETERMINE THAT THE GAS SUPPLY SYSTEM IS ADEQUATE,
 PLEASE SUBMIT TWO SETS OF A GAS ISOMETRIC RISER DIAGRAM
 FOR THE PROJECT. SPECIFY THE PIPE MATERIAL, SIZE AND
 LENGTHS, THE REQUIRED BTUS OF EACH APPLIANCE, THE TYPE
 OF GAS (LP OR NATURAL), THE SYSTEM PRESSURE, SPECIFY
 THE TOTAL DISTANCE FROM THE POINT OF DELIVERY TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND THE SIZING TABLE
 THAT WAS USED TO DESIGN THE SYSTEM. FBC CHAPTER 24.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714