| 2012-02-15 16:53:16 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND |
| | THE PLANS SPECIFY CATEGORY B. PLEASE CORRECT. FBCR |
| | 301.2.1.4.3 |
| | |
| | 2) REVISE THE PRESSURES IN THE WINDOW AND DOOR SCHEDULE |
| | ON A-2 TO CONFORM WITH EXPOSURE C. FBCR 301.2.1 |
| | |
| | 3) SHOW COMPLIANCE WITH FBCR 320 FOR TERMITE PROTECTION |
| | ON THE PLANS. |
| | |
| | 4) PROVIDE A WINDOW BUCK FASTENING DETAIL IN COMPLIANCE |
| | WITH FBC R613.6. |
| | |
| | 5) THE SECTION DETAIL FOR SECTION 61 ON S1 IS NOT |
| | PROVIDED. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 |
| | |
| | 6) THE FOOTING FOR THE MASONRY WALL AT THE EXPANDED |
| | COVERED PATIO IS INCORRECTLY LABELED AS F1 ON SHEET |
| | S-1. IT SHOULD BE FOOTER F-3. PLEASE CORRECT. FBC |
| | R403.1.1 |
| | |
| | 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 106.3.3 |
| | |
| | 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | STRUCTURAL MULLIONS AND THE ROOFING MATERIAL AS |
| | REQUIRED BY DCA RULE 9N-3. |
| | |
| | 9) THE TRANSOM WINDOW LABELED #001 AND THE PICTURE |
| | WINDOW LABELED #016 ARE LARGER THAN THE MAXIMUM SIZE |
| | ALLOWED BY THE FIXED GLASS PRODUCT APPROVAL THAT WAS |
| | SUBMITTED FOR THE FIXED WINDOWS. PLEASE SUBMIT THE |
| | APPROPRIATE PRODUCT APPROVALS AS REQUIRED BY DCA RULE |
| | 9N-3. IF THESE ARE SMALLER WINDOWS THAT ARE MULLED |
| | TOGETHER PLEASE PROVIDE THIS INFORMATION ON THE PLANS. |
| | |