2012-04-09 16:14:05MECHANICAL PROVISO
  
 AIR-HANDLERS LOCATED IN ATTICS SHALL COMPLY WITH FBCR
 M1305.1.3 AND M1305.1.3.2. THE SERVICE PANEL OF THE
 EQUIPMENT SHALL BE LOCATED WITHIN 6 FEET OF AN ATTIC
 ACCESS. THE ACCESS SHALL BE OF SUFFICIENT SIZE TO
 REPLACE THE UNIT. A PASSAGE WAY NOT LESS THAN 30 INCHES
 HIGH AND 22 INCHES WIDE AND NOT MORE THAN 6 FEET IN
 LENGTH WITH CONTINUOUS SOLID FLOORING NOT LESS THAN 24
 INCHES WIDE IS REQUIRED.