| Plan Review Notes For Permit 12010525 |
| Permit Number |
12010525 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-04-09 16:14:05 | MECHANICAL PROVISO | | | | | | AIR-HANDLERS LOCATED IN ATTICS SHALL COMPLY WITH FBCR | | | M1305.1.3 AND M1305.1.3.2. THE SERVICE PANEL OF THE | | | EQUIPMENT SHALL BE LOCATED WITHIN 6 FEET OF AN ATTIC | | | ACCESS. THE ACCESS SHALL BE OF SUFFICIENT SIZE TO | | | REPLACE THE UNIT. A PASSAGE WAY NOT LESS THAN 30 INCHES | | | HIGH AND 22 INCHES WIDE AND NOT MORE THAN 6 FEET IN | | | LENGTH WITH CONTINUOUS SOLID FLOORING NOT LESS THAN 24 | | | INCHES WIDE IS REQUIRED. |
|