| Plan Review Notes For Permit 12010525 |
| Permit Number |
12010525 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-31 08:58:01 | 12010525 | | | 335 KENILWORTH BLVD. | | | INTERIOR RENOVATION | | | | | | PROVIDE AN ELECTRICAL RISER PLAN SHOWING THE MAIN | | | DISCONNECTS GROUNDING AND SERVICE CONDUCTORS. AN | | | INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND NEC 250.94, NEC 215.5 | | | PROVIDE A GFCI PROTECTED RECEPTACLE AT EACH ENTRANCE. | | | NEC 210.52 | | | ALL RECEPTACLES SERVING KITCHEN COUNTER TOP SURFACES | | | MUST BE GFCI PROTECTED. NEC 210.8 | | | LOAD CALCULATION DID NOT INCLUDE AN ELECTRIC RANGE. NEC | | | 220.10 | | | IF THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE | | | OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | | R313 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|