2012-01-31 08:58:0112010525
 335 KENILWORTH BLVD.
 INTERIOR RENOVATION
  
 PROVIDE AN ELECTRICAL RISER PLAN SHOWING THE MAIN
 DISCONNECTS GROUNDING AND SERVICE CONDUCTORS. AN
 INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND NEC 250.94, NEC 215.5
 PROVIDE A GFCI PROTECTED RECEPTACLE AT EACH ENTRANCE.
 NEC 210.52
 ALL RECEPTACLES SERVING KITCHEN COUNTER TOP SURFACES
 MUST BE GFCI PROTECTED. NEC 210.8
 LOAD CALCULATION DID NOT INCLUDE AN ELECTRIC RANGE. NEC
 220.10
 IF THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
  