2012-02-13 14:57:262007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE ENGINEER OF RECORD SIGNED AND DATED THE PLANS,
 BUT DID NOT SEAL THEM AS REQUIRED BY FS 471.025 (1).
  
 2) THE ENERGY CALCULATIONS FOR EACH UNIT ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT PER FBCR ENERGY GLITCH
 AMENDMENTS N1100.2.2.
  
 3) PLAN SHEET S-1 SPECIFIES A LARGE MISSILE IMPACT
 RATED BATHROOM WINDOW AND EXPIRED NOA #07-0815.09. THE
 PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR A NON-IMPACT
 WINDOW. PLEASE CLARIFY. CITY AMENDMENTS 106.1
  
 4) PLEASE CLARIFY WHICH WINDOWS ON THE PLANS ARE BEING
 REPLACED. CITY AMENDMENTS 106.1
  
 5) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR PROTECTION
 OF GLAZED OPENINGS. PROVIDE TWO COPIES OF THE
 FOLLOWING: PRODUCT APPROVAL FOR THE STORM PANELS, KEY
 PLAN AND INSTALLATION SCHEDULE.
  