| 2012-08-22 16:32:30 | BUILDING PLAN REVIEW |
| | PERMIT: 12010509 |
| | ADD: 805 20TH ST |
| | CONT: VICTORY ENGINEERING & GENERAL CONTRACTORS |
| | TEL: (305)244-5424 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 1A) COMPLIED. |
| | |
| | 1B) SEMI-COMPLIED. |
| | PLEASE INDICATE WHAT PERCENTAGE OF GLAZED OPENINGS WERE |
| | REPLACED, 2007/09 EXST BLDG CODE 606.4 REQUIRES EITHER |
| | LARGE MISSILE IMPACT RATED WINDOWS OR STORM SHUTTERS. |
| | EXCEPTION IF 25% OR LESS OF THE GLAZED AREA OF WINDOWS |
| | AND DOORS WERE REPLACED THEN STORM SHUTTERS ARE NOT |
| | REQUIRED. |
| | A PRODUCT APPROVAL FOR STORM SHUTTERS WAS PROVIDEDED |
| | BUT NONE OF THE DETAILS INDICATING THE TYPE |
| | CONFIGURATION FOR THE TOP AND BOTTOM COMPONENENTS OR IF |
| | SIDE ANCHORS ARE GOING TO BE INSTALLED. ANCHORS TO BE |
| | INSTALLED INTO WOOD FRAMING, CBS BLOCK, FILLED OR |
| | NON-FILLED BLOCK OR IF 3000 PSI CONCRETE. ANCHORS TYPES |
| | ARE NOT CIRCLED NOR IS THE PRESSURES OR SPANS. |
| | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1609.1.4. |
| | |
| | FL BLD CODE 2004 SECTION 106.3.3, |
| | 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY |
| | HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT |
| | STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| | APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE. |
| | |
| | NEW COMMENT: |
| | 2) THE NEW WINDOW SCHEDULE ON SHEET A-1 INDICATES |
| | WINDOW TYPES A & F, WINDOW TYPE A IS WIDER THAN SPANS |
| | IN THE PRODUCT APPROVAL WILL NEED MULLIONS AND WINDOW |
| | TYPE |
| | F IS TO LONG OF LENGTH (HEIGHT) THE PLANS INDICATE A |
| | HEIGHT OF 79" WHERE THE PRODUCT APPROVAL LONGEST |
| | WINDOWS (HEIGHT) IS 74 INCHES. |
| | |
| | 3) THE NEW MULLION REPORT SUBMITTED NOA 11-1213.07 |
| | PLEASE CIRCLE THE MULLION WITH APPROPRIATE LENGTH AND |
| | PRESSURES FOR THE REQUIRED PRESSURES. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |