| Plan Review Notes For Permit 12010494 |
| Permit Number |
12010494 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-30 11:50:59 | SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED. | | | ADDITIONAL INFORMATION MAY BE NEEDED. PLEASE PROVIDE | | | THE FOLLOWING: | | | | | | INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL. | | | PROVIDE A PANEL SCHEDULE AND SUMMARY LOAD CALCULATION. | | | SHOW THE SERVICE LOCATION, FEEDER SIZE AND EXISTING | | | MAIN BREAKER. INCLUDE A FLOOR PLAN SHOWING THE LOCATION | | | OF ALL NEW AND EXISTING OUTLETS INCLUDING LIGHTING. NEC | | | 215.5 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | VERIFY THE BATHROOM RECEPTACLES ARE GFCI PROTECTED. NEC | | | 210.8 | | | INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER | | | RESISTANT. NEC 406.11 | | | ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE | | | PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC | | | 210.12 | | | BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED | | | OUTSIDE FRONT AND BACK. NEC 210.70 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|