| Plan Review Notes For Permit 12010484 |
| Permit Number |
12010484 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-05-01 09:04:27 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED | | | IMPROVEMENT. WIND DESIGN CRITERIA, ALONG WITH SIGNATURE | | | AND SEAL (IF APPLICABLE) FOR INDIDUAL LICENSED TO | | | DESIGN THIS SCOPE OF WORK, FS471, 481, 489. | | | | | | 2ND REVIEW - COMMENT NOT ADDRESSED COMPLETELY. A DETAIL | | | WAS PROVIDED BUT WIND DESIGN CRITERIA (MINIMUM OF | | | 140MPH EXPOSURE C), DESIGNER INFORMATION NOT ON PLAN. | | | | | | 3RD REVIEW - PLAN DOES NOT INCLUDE THE WIND DESIGN | | | CRITERIA, WALL INSULATION DOES NOT MEET MINIMUMS | | | REQUIRED BY ENERGY CALCS. THE INDIVIDUAL TAKING | | | RESPONSIBILITY FOR THE PLAN IS TO PROVIDE NAME AND | | | SIGNATURE. | | | | | | 2-4. OK. | | | | | | 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR | | | THE SLIDING GLASS DOOR, FAC9N-3. | | | | | | 2ND REVIEW, PRODUCT APPROVAL SUBMITTED IS EXPIRED. | | | PROVIDE CURRENT PRODUCT APPROVAL FOR SLIDING GLASS DOOR | | | AND FOR THE SHUTTERS. | | | | | | 3RD REVIEW, PRODUCT APPROVAL SUBMITTED IS FOR WALL | | | PANELS/SIDING. PROVIDE THE PRODUCT APPROVAL FOR THE | | | SLIDING GLASS DOOR, FAC9N-3. | | | | | | 6. OK. | | | | | | | | | |
|