2012-05-01 09:04:27****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED
 IMPROVEMENT. WIND DESIGN CRITERIA, ALONG WITH SIGNATURE
 AND SEAL (IF APPLICABLE) FOR INDIDUAL LICENSED TO
 DESIGN THIS SCOPE OF WORK, FS471, 481, 489.
  
 2ND REVIEW - COMMENT NOT ADDRESSED COMPLETELY. A DETAIL
 WAS PROVIDED BUT WIND DESIGN CRITERIA (MINIMUM OF
 140MPH EXPOSURE C), DESIGNER INFORMATION NOT ON PLAN.
  
 3RD REVIEW - PLAN DOES NOT INCLUDE THE WIND DESIGN
 CRITERIA, WALL INSULATION DOES NOT MEET MINIMUMS
 REQUIRED BY ENERGY CALCS. THE INDIVIDUAL TAKING
 RESPONSIBILITY FOR THE PLAN IS TO PROVIDE NAME AND
 SIGNATURE.
  
 2-4. OK.
  
 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE SLIDING GLASS DOOR, FAC9N-3.
  
 2ND REVIEW, PRODUCT APPROVAL SUBMITTED IS EXPIRED.
 PROVIDE CURRENT PRODUCT APPROVAL FOR SLIDING GLASS DOOR
 AND FOR THE SHUTTERS.
  
 3RD REVIEW, PRODUCT APPROVAL SUBMITTED IS FOR WALL
 PANELS/SIDING. PROVIDE THE PRODUCT APPROVAL FOR THE
 SLIDING GLASS DOOR, FAC9N-3.
  
 6. OK.
  
  
  