Plan Review Notes
Plan Review Notes For Permit 12010484
Permit Number 12010484
Review Stop B
Sequence Number 1
Notes
Date Text
2012-02-06 10:46:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED
 IMPROVEMENT. WIND DESIGN CRITERIA, ALONG WITH SIGNATURE
 AND SEAL (IF APPLICABLE) FOR INDIDUAL LICENSED TO
 DESIGN THIS SCOPE OF WORK, FS471, 481, 489.
  
 2. IMPACT FEE ASSESSMENT REQUIRED BY PALM BEACH COUNTY,
 233-5025 FOR MORE INFORMATION.
  
 3. A LIVING ROOM IS PROPOSED, BUT NO INFORMATION
 PROVIDED REGARDING DRYWALL INSTALLATION, PLEASE CLARIFY
 SCOPE.
  
 4. ENERGY CALCS REQUIRED, FBC 13-103.
  
 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE SLIDING GLASS DOOR, FAC9N-3.
  
 6. MINIMUM PLAN REVIEW CRITERIA, PROVIDE ELEVATION OF
 EXISTING, PROPOSED.
  
  
  