| Plan Review Notes For Permit 12010467 |
| Permit Number |
12010467 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-27 13:08:47 | 701 NORTHPOINT PARKWAY - SUITE #500 | | | PERMIT #12010467 | | | MASTER #11110281 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | INDICATE ROOM NAMES ON PLANS AND INDICATE THE LOCATION | | | OF EXISTING FIRE ALARM DEVICES TO VERIFY SUFFICIENT | | | COVERAGE EXISTS FOR THE ENTIRE FLOOR. | | | | | | THE QUALIFIED SYSTEM DESIGNER SHALL BE IDENTIFIED ON | | | THE PLANS. | | | | | | INDICATE THE ADDRESS OF THE NEW DUCT SMOKE DETECTOR. | | | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|