Plan Review Notes
Plan Review Notes For Permit 12010451
Permit Number 12010451
Review Stop M
Sequence Number 3
Notes
Date Text
2012-03-23 13:56:47RESIDENTIAL (R3) MECHANICAL REVIEW THIRD CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
  
 ORIGINAL COMMENT:
 1- INFORMATION SUBMITTED ON THE ENERGY CALCULATIONS
 DOESN'T MATCH INFORMATION SUBMITTED ON THE RESIDENTIAL
 SYSTEM SIZING CALCULATIONS. REVISE ENERGY CALCULATIONS
 AS REQUIRED TO MATCH. CHECK THE TOTAL COOLING CAPACITY
 AND TOTAL HEATING CAPACITY.
  
 RESPONSE TO RE-SUBMITAL:
 REVISED ENERGY CALCULATIONS STATE "REPLACEMENT FOR
 WHOLEHOUSE". THIS INFORMATION IS INCOMPLETE BECAUSE
 EVEN IF IT'S A REPLACEMENT, THEN, THE CAPACITY SHALL
 MATCH THE EQUIPMENT SIZING CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712