2012-02-08 15:33:27RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- INFORMATION SUBMITTED ON THE ENERGY CALCULATIONS
 DOESN'T MATCH INFORMATION SUBMITTED ON THE RESIDENTIAL
 SYSTEM SIZING CALCULATIONS. REVISE ENERGY CALCULATIONS
 AS REQUIRED TO MATCH. CHECK THE TOTAL COOLING CAPACITY
 AND TOTAL HEATING CAPACITY.
  
 2- BOTH MECHANICAL DRAWINGS NEED TO HAVE THE
 ARCHITECT'S ORIGINAL EMBOSSED SEAL AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTES. ONLY ONE COPY SUBMITTED
 HAS EMBOSSED SEAL.
  
  