| Plan Review Notes For Permit 12010451 |
| Permit Number |
12010451 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-08 15:33:27 | RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- INFORMATION SUBMITTED ON THE ENERGY CALCULATIONS | | | DOESN'T MATCH INFORMATION SUBMITTED ON THE RESIDENTIAL | | | SYSTEM SIZING CALCULATIONS. REVISE ENERGY CALCULATIONS | | | AS REQUIRED TO MATCH. CHECK THE TOTAL COOLING CAPACITY | | | AND TOTAL HEATING CAPACITY. | | | | | | 2- BOTH MECHANICAL DRAWINGS NEED TO HAVE THE | | | ARCHITECT'S ORIGINAL EMBOSSED SEAL AS REQUIRED BY | | | CHAPTER 481 FLORIDA STATUTES. ONLY ONE COPY SUBMITTED | | | HAS EMBOSSED SEAL. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|