| 2012-02-15 09:12:34 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) PLEASE REVISE THE DESIGN CRITERIA ON SHEET 1.1 TO |
| | REFERENCE ASCE 7-05. FBCR CHAPTER 43. |
| | |
| | 2) UNDER THE EXISTING BUILDING NOTE ON SHEET 1.1 PLEASE |
| | CHANGE FROM 2004 FBC TO THE CODE IN EFFECT WHICH IS THE |
| | 2007 FBC. |
| | |
| | 3) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED |
| | BY THE 2007 FBCR ENERGY GLITCH AMENDMENTS N 1100. |
| | |
| | 4) THE POCKET DOOR TO THE ROOM CONTAINING THE WATER |
| | CLOSET IS REQUIRED TO HAVE A 29" CLEAR OPENING. FL |
| | ACCESSIBILITY CODE SECTION 11-4.22.2 |
| | |
| | 5) ON SHEET 4.1 THE PLAN SPECIFIES ALL EXTERIOR DOORS |
| | TO BE THERMA-TRU WITH CLEAR GLASS, HOWEVER, THE PRODUCT |
| | APPROVALS THAT WERE SUBMITTED ARE FROM MASONITE |
| | INTERNATIONAL. PLEASE CLARIFY. CITY AMENDMENTS 106.1.1 |
| | |
| | 6) NOTE (1) FOR THE TRUSS ANCHOR SCHEDULE ON SHEET 5.1 |
| | SAYS TO SEE ANCHOR DETAILS ON S-4 FOR THE REQUIRED |
| | FASTENERS. THERE IS NO SHEET S-4. THE DETAILS ARE ON |
| | SHEET 6.2. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 |
| | |
| | 7) THE FLORIDA PRODUCT APPROVAL NUMBERS AND THE ANCHOR |
| | CAPACITIES LISTED IN THE TRUSS ANCHOR SCHEDULE ON SHEET |
| | 5.1 ARE NOT CORRECT. PLEASE REVISE. DCA RULE 9N-3 & FBC |
| | R802.1.6.5 |
| | |
| | 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 106.3.3 |
| | |
| | 9) PLEASE UPDATE THE DESIGN CRITERIA IN THE WINDOW AND |
| | DOOR PRESSURE TABLE ON SHEET 6.2 TO THE 2007 FBC AND |
| | ASCE 7-05. FBCR CHAPTER 43 |
| | |
| | 10) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | DOUBLE OUTSWING GLAZED DOORS HAS A MAXIMUM DESIGN |
| | PRESSURE OF - 55 PSF AND THE PLAN REQUIRES -58 PSF |
| | ACCORDING TO THE TABLE ON SHEET 6.2. PLEASE PROVIDE |
| | PRODUCT WITH ADEQUATE DESIGN PRESSURES. DCA RULE 9N-3 |
| | |
| | 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE SIX |
| | PANEL METAL FRONT DOOR THAT IS SPECIFIED ON THE PLANS. |
| | DCA RULE 9N-3 |
| | |
| | 12) PLEASE SUBMIT A RESPONSE LETTER THAT INDICATES HOW |
| | EACH OF THE REVIEW COMMENTS WAS ADDRESSED. |
| | |