| Date |
Text |
| 2012-02-24 12:19:45 | 2013 PONCE DE LEON AVENUE |
| | PERMIT #12010446 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | INDICATE THE LABORATORY CLASS (CLASS A, B, C OR D) PER |
| | NFPA 45 - FIRE PROTECTION FOR LABORATORIES USING |
| | CHEMICALS. |
| | |
| | PER NFPA 45, LABORATORY SPACES SHALL BE SEPARATED FROM |
| | NON-LABORATORY SPACES WITH A 1-HOUR FIRE RATING. |
| | |
| | THE EGRESS AND LIFE SAFETY REQUIREMENTS FOR |
| | NON-INSTRUCTIONAL LAB UNITS SHALL COMPLY WITH |
| | INDUSTRIAL OCCUPANCIES (CHAPTER 40) OF NFPA 101. |
| | |
| | INDICATE THE PRESENCE AND QUANTITIES OF ANY HAZARDOUS |
| | CHEMICALS, FLAMMABLE LIQUIDS, FLAMMABLE GASES, ETC. |
| | |
| | PROVIDE A LAYOUT OF THE LABORATORY EQUIPMENT (FUME |
| | HOODS, REFRIGERATORS, SPECIMEN STORAGE, CHEMICAL |
| | STORAGE, ETC). |
| | |
| | ENTRANCES TO LABORATORY UNITS, LABORATORY WORK AREAS |
| | AND STORAGE AREAS SHALL BE IDENTIFIED BY SIGNS TO WARN |
| | EMERGENCY RESPONSE PERSONNEL OF UNUSUAL OR SEVERE |
| | HAZARDS THAT ARE NOT DIRECTLY RELATED TO THE FIRE |
| | HAZARD OF CONTENTS. |
| | |
| | EXHAUST SYSTEMS USED FOR THE REMOVAL OF HAZARDOUS |
| | MATERIALS SHALL BE IDENTIFIED TO WARN PERSONNEL OF THE |
| | POSSIBLE HAZARDS. |
| | |
| | LABEL CONTAINERS AND CONTENT, INCLUDING PRECAUTIONARY |
| | INFORMATION, SHALL BE PROVIDED DIRECTLY ON ALL ORIGINAL |
| | AND SUBSEQUENT CONTAINERS OF HAZARDOUS CHEMICALS, |
| | EXCEPT THOSE BEING USED IN ONGOING EXPERIMENTS. |
| | |
| | EACH REFRIGERATOR, FREEZER, OR COOLER SHALL BE |
| | PROMINENTLY MARKED TO INDICATE WHETHER OR NOT IT MEETS |
| | THE REQUIREMENTS FOR SAFE STORAGE OF FLAMMABLE LIQUIDS. |
| | |
| | REFRIGERATORS, FREEZERS, AND OTHER COOLING EQUIPMENT |
| | USED TO STORE OR COOL FLAMMABLE LIQUIDS SHALL BE |
| | DESIGNED FOR SUCH USE. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |