| 2012-01-27 09:51:14 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1. THE REMOVAL OF THE PLUMBING FIXTURES AS SHOWN ON | | | SHEET A-1 WOULD BRING THE FIXTURE COUNT BELOW THAT | | | REQUIRED FOR AN OCCUPANT LOAD OF 60 AND OCCUPANCY TYPE | | | OF BUSINESS. | | | 403.1 MINIMUM NUMBER OF FIXTURES. PLUMBING FIXTURES | | | SHALL BE PROVIDED FOR THE TYPE OF OCCUPANCY AND IN THE | | | MINIMUM NUMBER SHOWN IN TABLE 403.1. TYPES OF | | | OCCUPANCIES NOT SHOWN IN TABLE 403.1 SHALL BE | | | CONSIDERED INDIVIDUALLY BY THE CODE OFFICIAL. THE | | | NUMBER OF OCCUPANTS SHALL BE DETERMINED BY THE FLORIDA | | | BUILDING CODE, BUILDING. OCCUPANCY CLASSIFICATION SHALL | | | BE DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING | | | CODE, BUILDING. | | | 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE | | | REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR | | | EACH SEX. | | | 403.3 NUMBER OF OCCUPANTS OF EACH SEX. THE REQUIRED | | | WATER CLOSETS, LAVATORIES, AND SHOWERS OR BATHTUBS | | | SHALL BE DISTRIBUTED EQUALLY BETWEEN THE SEXES BASED ON | | | THE PERCENTAGE OF EACH SEX ANTICIPATED IN THE OCCUPANT | | | LOAD. THE OCCUPANT LOAD SHALL BE COMPOSED OF 50 PERCENT | | | OF EACH SEX, UNLESS STATISTICAL DATA APPROVED BY THE | | | CODE OFFICIAL INDICATE A DIFFERENT DISTRIBUTION OF THE | | | SEXES (SEE ALSO SECTION 403.1.1). | | | 2 RESTROOMS FOR WOMEN AND 2 RESTROOMS FOR MEN WILL BE | | | REQUIRED. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|