2012-01-27 09:51:14FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. THE REMOVAL OF THE PLUMBING FIXTURES AS SHOWN ON
 SHEET A-1 WOULD BRING THE FIXTURE COUNT BELOW THAT
 REQUIRED FOR AN OCCUPANT LOAD OF 60 AND OCCUPANCY TYPE
 OF BUSINESS.
 403.1 MINIMUM NUMBER OF FIXTURES. PLUMBING FIXTURES
 SHALL BE PROVIDED FOR THE TYPE OF OCCUPANCY AND IN THE
 MINIMUM NUMBER SHOWN IN TABLE 403.1. TYPES OF
 OCCUPANCIES NOT SHOWN IN TABLE 403.1 SHALL BE
 CONSIDERED INDIVIDUALLY BY THE CODE OFFICIAL. THE
 NUMBER OF OCCUPANTS SHALL BE DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING. OCCUPANCY CLASSIFICATION SHALL
 BE DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
 403.3 NUMBER OF OCCUPANTS OF EACH SEX. THE REQUIRED
 WATER CLOSETS, LAVATORIES, AND SHOWERS OR BATHTUBS
 SHALL BE DISTRIBUTED EQUALLY BETWEEN THE SEXES BASED ON
 THE PERCENTAGE OF EACH SEX ANTICIPATED IN THE OCCUPANT
 LOAD. THE OCCUPANT LOAD SHALL BE COMPOSED OF 50 PERCENT
 OF EACH SEX, UNLESS STATISTICAL DATA APPROVED BY THE
 CODE OFFICIAL INDICATE A DIFFERENT DISTRIBUTION OF THE
 SEXES (SEE ALSO SECTION 403.1.1).
 2 RESTROOMS FOR WOMEN AND 2 RESTROOMS FOR MEN WILL BE
 REQUIRED.
  