| Plan Review Notes For Permit 12010446 |
| Permit Number |
12010446 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-30 10:02:48 | PLANS DENIED | | | 1) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3 2007 | | | FBC (M) | | | 2) PROVIDE A DETAIL ON THE PLANS BY THE ENGINEER ON THE | | | CURB | | | TO ROOF TIEDOWN AND UNIT TO CURB TIEDOWN PER SECTION | | | 301.12 | | | WIND RESISTANCE 2007 FBC (M) . | | | 3) REFER TO SECTION 13-409.AB.3.3 SHUT OFF DAMPER | | | CONTROLS. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|