2012-01-30 10:02:48PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3 2007
 FBC (M)
 2) PROVIDE A DETAIL ON THE PLANS BY THE ENGINEER ON THE
 CURB
 TO ROOF TIEDOWN AND UNIT TO CURB TIEDOWN PER SECTION
 301.12
 WIND RESISTANCE 2007 FBC (M) .
 3) REFER TO SECTION 13-409.AB.3.3 SHUT OFF DAMPER
 CONTROLS.