| Plan Review Notes For Permit 12010446 |
| Permit Number |
12010446 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-27 11:33:51 | 2013 PONCE DE LEON AVENUE | | | PERMIT #12010446 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO | | | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION | | | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | DUCT SMOKE DETECTORS AND REMOTE TEST STATION ARE NEEDED | | | FOR MECHANICAL AIRFLOWS GREATER THAN 2000 CFM. | | | | | | INDICATE THE USE OF THE LARGE SPACE CONTAINING THE | | | EXISTING SAFETY SHOWER. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|