Plan Review Notes
Plan Review Notes For Permit 12010446
Permit Number 12010446
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-26 09:00:20BUILDING PLAN REVIEW
 PERMIT: 12010446
 ADD: 2013 PONCE DE LEON AVE
 CONT: GLOBAL LINK SYSTEMS
 TEL: (954)448-8847
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COVER SHEET :
  
 1A) THE PLANS INDICATE THEY ARE IN COMPLIANCE WITH THE
 STANDARD BUILDING CODE. THE STANDARD BUILDING CODE HAS
 NOT BEEN EXISTANCE SINCE THE 2001 FBC-B WAS ADOPTED.
 CURRENTLY THE 2007/09 FBC-B IS THE ADOPTED STATE-WIDE
 CODE. THE 2007/09 EXISTING BUILDING CODE FOR
 ALTERATIONS TO BUILDINGS THAT HAVE BEEN ALREADY CO'ED
 FOR ALTERATIONS AND CHANGE OF OCCUPANCY.
  
 1B) THE SECOND ISSUE WITH THE COVER SHEET IS THE
 MINIMUM BUILDING TYPE VI. WHEN THE 2001 FBC-B WAS
 ADOPTED THE BUILDING TYPE VI IS NO LONGER IN EXISTANCE.
 THE 2004 FBC-B CODE COMMENTARY HAS CONSTRUCTION TYPE
 COMPARISION FIGURE 600, UNDER THE SBC BUILDING TYPE VI
 IS A TYPE VB UNDER THE 2004 FBC-B. THE 2007/09 FBC-B
 STILL LIST THE MINIMIUM BUILDING YPE AS TYPE VB.
  
 1C) THE COVERSHEET ALSSO INDICATES TTHE TOTAL SQ FT OF
 THE BUILDING AS 5,987 SQ FT THE TOTAL OCCUPANT LOAD
 SHOULD BE 60 NOT 59 AS TAKEN IN UNDER THE OCCUPANT
 LOAD.
 2007/09 FBC-B TABLE 1004.1.1.
  
 2) SHEET A-2 THE RIGHT SIDE OF THE PAGE INDICATES 8 OF
 15 WORK STATIONS THAT CREATE POSSIBLY A DEAD END
 CORRIDOR OVER 20'-0" LONG IF THE EXISTING OFFICE # 2
 DOOR IS LOCKED.
 FBC-B 1017.3.
  
 3) PLEASE REVIEW SHEET A4 THE REFLECTED CEILING PLAN,
 A5 LIFE SAFETY PLAN VERSES SHEET E2 FOR EXIT SIGNS AND
 EMERGENCY LIGHTS WITH BATTERY BACK-UP. THERE SEEMS TO
 BE A DICREPANCY IN THE PLANS. A4 & A5 APPEAR TO BE
 MISSING FIXTURES. 2007/09 FBC-B 1006.2 & 1006.3.
  
 4) NEITHER SHEET A2 OR A5 PROVIDE INFORMATION AS TO
 COMPLIANCE OF FBC-B 906.1 LOCATION OF PORTABLE FIRE
 EXTINGUISHERS, A2 LEGEND DOES NOT EVEN HAVE A SYMBLE
 FOR FIRE EXTINGUISHERS.
  
 5) SHEET A3 DETAIL TYP EXTERIOR WALL SECTION INDICATES
 INSTALL NEW R-19 INSULATION OVER EXISTING DECKING AS
 REQUIRED. THE CONFUSION IS NO ROOFING PERMIT IS PULLED
 FOR APPLYING INSULATION OVER THE ROOF DECK, THE PLANS
 SHOW A CROSS HATCHING UNDER THE DECK AS IF THIS
 INSULATION WOULD BE HUNG, THESE A RE BAR JOIST
 DEPICTED, HOW WILL THE INSULATION BE INSTALLED. 106.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET A3 ALSO INDICATES A DETAIL (K) OF A BREAK ROOM
 SINK THE DETAIL INDICATES A 34" HIGH TOP AND ACCESSIBLE
 SINK BUT FAILS TO PROVIDE COMPLIANCE FOR A FORWARD
 APPROACH AND CLEAR FLOOR SPACE.PLEASE SEE 2007/09 FBC-B
 11-24. 1-7.
  
 7) SHEET A3 DETAIL (K) DOES NOT INDICATE AT WHAT HEIGHT
 THE DRINKING FOUNTAIN HEIGHT (SPOUT) WILL BE INSTALLED
 . 2007/09 FBC-B 11-4.15.2.
  
 8) THE PERMIT APPLICATION INDICATES THE VALUE OF THIS
 PROJECT TO BE $78,000 DOLLARS FBC-B11-4.1.6(2)
 (1)(2)(A) DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE
 EVENT OF DISPROPORTIONALITY. $78,000 X .20%= $
 15,600.00 IN UPGRADES TO BRING THE BUILDING IN
 CONFORMANCE TO CURRENT ACCESSIBILITY STANDARDS. THE
 MONIES ARE TO BE SPENT IN THIS ORDER:
 (I) AN ACCESSIBLE ENTRANCE, ENTRANCE AND EXTERIOR
 EGRESS NOT SHOWN STAIRS, RAMPS ETC?
 (II) AN ACCESSIBLE ROUTE TO ALTERED AREAS
 (III) AT LEAST ON ACCESSIBLE RESTROOM FOR EACH SEX OR A
 SINGLE UNISEX RESTROOM
 (IV) AN ACCESSIBLE TELEPHONE
 (V) ACCESSIBLE DRINKING FOUNTAIN
 (VI) PARKING STORAGE AND ALARMS
 PLEASE PROVIDE DOCUMENTATION FOR CODE COMPLIANCE FOR
 THE LISTED ABOVE ACCESSIBILITY ITEMS AND DOLLAR AMOUNT
 SPENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  