| 2012-01-24 13:34:22 | BUILDING PLAN REVIEW |
| | PERMIT: 12010419 |
| | ADDRESS: 3101 OKEECHOBEE BLVD |
| | CONT: DREAMWORKS ELECTRICAL SERVICES |
| | TEL: (772)341-9818 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET PV-8 STRUCTURAL SHEET INDICATES THIS TO BE IN |
| | A B EXPOSURE WHILE TO THE NORTH THERE IS A CLEAR PATH |
| | OVER 150 FEET WIDE AND 600 FEET LONG WHICH MAKES THIS A |
| | EXPOSURE C-TYPE WITH THE INCREASED PRESSURES. FBC-B |
| | 1609.4.3 EXPOSURE C/ AND ADJUSTMENT FACTOR OF 1.35 @ AN |
| | ELEVATION OF 25 FT. |
| | |
| | 2) PLEASE PROVIDE A ROOF PLAN WITH THE LOCATION OF THE |
| | SOLAR PHOTOVOLTAIC PANELS INDICATE WHICH PANELS ARE |
| | LOCATED IN ROOF ZONES 1, 2 & 3 WITH THE ASSOCIATED |
| | PRESSURES. |
| | |
| | 3) THE STRUCTURAL PLANS DO NOT PROVIDE THE TYPE OF |
| | ANCHORS OR SIZE OF ANCHOR TO BE USED IN THE INSTALATION |
| | TO THE ROOF DECK, NOR DOES THE PLAN INDICATE THE TYPE |
| | OF ROOF DECK |
| | THESE ANCHORS ARE BEING INSTALLED IN. THE PLANS |
| | INDICATE A PULL STRENGTH PER ANCHOR POINT BUT AGAIN |
| | WHAT TYPE OF MATERIAL IS THIS DESIGN ANCHORED TO? |
| | ADDITIONAL INFORMATION REQUIRED, MOMENT OF OVERTURNING, |
| | FBC-B 1609. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |