| Plan Review Notes For Permit 12010415 |
| Permit Number |
12010415 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-30 14:17:23 | 12010415 | | | 419 33RD STREET | | | NEW SFD | | | | | | PLEASE REDRAW THE ELECTRICAL RISER TO SHOW HOW EACH | | | PANEL BOARD WILL BE FED. LOCATE THE ELECTRIC PANEL | | | BOARDS ON THE PLAN. SHOW THE GROUNDING SYSTEM FOR EACH | | | SUB PANEL. NEC 215.5 | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. 2008 NEC 250.94 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | INDICATE THAT ALL GENERAL PURPOSE BRANCH CIRCUITS MUST | | | BE PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008 | | | NEC 210.12 | | | THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | ADD A GFCI PROTECTED RECEPTACLE TO SERVE EACH BASIN IN | | | THE SECOND FLOOR BATH. NEC 210.52 (D) | | | SMOKE DETECTORS ARE REQUIRED TO BE INTERCONNECT AND | | | LOCATED INSIDE AND OUTSIDE EACH SLEEPING AREA. FBC R | | | 313 | | | | | | ROBERT LECKY, CBO | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|