| Plan Review Notes For Permit 12010341 |
| Permit Number |
12010341 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-02 15:48:51 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE ENERGY CALCULATIONS ARE NOT COMPLETE. IT APPEARS | | | THAT THERE MAY HAVE BEEN AN ERROR WITH THE PRINTER. | | | PLEASE SUBMIT TWO COMPLETE COPIES OF THE ENERGY | | | CALCULATIONS AS REQUIRED BY N1100.2 OF THE 2007 FBC | | | ENERGY GLITCH AMENDMENTS. | | | | | | 2) THE HVAC SYSTEM HAS BEEN DESIGNED BY A DIFFERENT | | | MECHANICAL CONTRACTOR THAN THE ONE THAT IS SIGNED ON | | | THE PERMIT APPLICATION TO DO THE WORK. UNDER THE DESIGN | | | AND BUILD EXEMPTION TO FLORIDA STATUTE 471.003(2)(H), | | | THE MECHANICAL CONTRACTOR IS ALLOWED TO DESIGN THE | | | SYSTEM ONLY IF IT IS INSTALLED BY HIM. SINCE THIS IS | | | NOT THE CASE, THE MECHANICAL PLANS ARE REQUIRED TO BE | | | SIGNED AND SEALED BY THE DESIGN ENGINEER. | | | | | | 3) ON SHEET M2 BOTH OF THE AIR HANDLERS FOR THE SECOND | | | FLOOR ARE LABELED AHU #3. PLEASE CORRECT. CITY | | | AMENDMENTS 106.1.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|