| 2012-02-02 10:19:32 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. IMPACT FEE ASSESSMENT REQUIRED; CONTACT 561-233-5025 |
| | FOR MORE INFORMATION. |
| | |
| | 2. FIREPLACE SPECS REQUIRED, FBC R1005. THIS MAY BE |
| | SUBMITTED AT THIS TIME OR WILL BE PROVISO ITEM TO |
| | SUBMIT AS A REVISION. |
| | |
| | 3. PROVIDE PRODUCT APPROVALS FOR THE ENTRY DOOR, |
| | MULLION, SINGLE HUNG WINDOW, FAC9N-3. THIS MAY BE |
| | SUBMITTED AT THIS TIME OR WILL BE A PROVISO ITEM TO |
| | SUBMIT AS A REVISION AFTER ISSUANCE. |
| | |
| | 4. DESIGN PRESSURES ON ARCHITECTURAL SHEETS APPEAR TOO |
| | LOW (FOR EXAMPLE, SHEET A02) AND IN CONFLICT WITH |
| | STRUCTURAL SHEET S0, FBC R301. PLEASE REMOVE FROM |
| | AFFECTED SHEETS OR CORRELATE WITH STRUCTURAL SHEETS. |
| | |
| | 5. SHEET A.08, STRUCTURAL CRITERIA, INCORRECTLY STATES |
| | 100 MPH FASTEST MILE NON WIND BORNE DEBRIS REGION. |
| | OTHER AREAS OF PLAN CORRECTLY DECLARE WIND DESIGN |
| | CRITERIA AS 140MPH, EXPOSURE C. AS THIS APPEARS TO BE A |
| | TYPO, PLEASE REMOVE LANGUAGE FROM PLAN TO AVOID |
| | POSSIBLE CONFLICTS, FBC R301. IF THIS IS NOT A TYPO AND |
| | IS DESIGN INTENT, PLEASE CONTACT ME TO DISCUSS. |
| | |
| | 6. M2, PROVIDE PRODUCT APPROVAL FOR THE MIAMI TECH CU |
| | TIE DOWNS, FAC9N 3. PLAN STATES THAT THESE ARE TO BE |
| | INSTALLED IN ACCORDANCE WITH MANUFACTURER?S |
| | INSTRUCTIONS, BUT I WAS UNABLE TO LOCATE THE PRODUCT |
| | WITH THIS DESCRIPTION ON THE INTERNET. PROVIDE SPEC |
| | SHEETS AND FASTENING PATTERN/CONFIGURATION TO SHOW HOW |
| | THE UNIT WILL RESIST WIND LOADS, FBC R301. |
| | |
| | 7. PROVIDE ORIGINAL SOILS INVESTIGATION REPORT, FS471. |
| | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS. |
| | |
| | 8. ENERGY CALCS ARE INCOMPLETE. PLEASE PROVIDE CORRECT |
| | ENERGY CALCS, FBC 13 103.1.1.2. PREPARER AND |
| | OWNER/AGENT ARE TO READY ENERGY CALCS AND CERTIFY AS TO |
| | ACCURACY PRIOR TO SIGNING. |
| | |
| | |
| | |