Plan Review Notes
Plan Review Notes For Permit 12010311
Permit Number 12010311
Review Stop B
Sequence Number 2
Notes
Date Text
2012-03-01 14:43:48****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. LIFE SAFETY PLAN SHOWS THE DOOR AS AN "EXIT ACCESS
 DOOR" BUT DOES NOT SHOW TRAVEL DISTANCE TO THE EXIT.
  
 2. PLEASE EXPLAIN RATIONALE OF SHOWING THIS DOOR AS AN
 EXIT WHEN IT DIRECTS OCCUPANTS FROM A RATED EXIT
 THROUGH AN INTERVENING SPACE. EXITS ARE TO BE
 CONTINUOUS TO THE EXIT DISCHARGE. PERHAPS THIS IS A
 CONVENIENCE DOOR TO BE MARKED CLEARLY AS "NOT AN EXIT"?
  
 IF THE INTENT IS FOR THIS NEW DOOR TO BE AN EXIT ACCESS
 FROM THE GARAGE TO THE EXIT CORRIDOR, PLEASE SHOW
 OCCUPANT LOAD OF GARAGE AS THE DOOR WOULD THEN BE
 SWINGING AGAINST THE DIRECTION OF TRAVEL FBC1008.1.2.
 ALSO IT APPEARS THAT THE STAIR DOOR WOULD BLOCK THE
 NEWLY CREATED CORRIDOR MORE THAN PERMITTED BY
 FBC1005.2.
  
 PLEASE FEEL FREE TO CONTACT ME FOR FURTHER ASSISTANCE.
  
  
  